Tutorial: Level control of coupled water tanks¶
| You will learn | a nonlinear process, linearization at an operating point, PI design for a second-order process, gain scheduling, actuator limits |
| Before this | DC motor speed and position control |
| Level and time | intermediate, about 40 minutes |
| Follow along | start the editor (uv run nervus), File ▸ Open examples/coupled_tanks.nervus, press ▶ and double-click the scopes; the figures below come from the same model |
| Topic | Control engineering ▸ Classic lab experiments (all tutorials) |
examples/coupled_tanks.py is the process-control experiment of many lab courses: a pump fills an upper tank,
the water runs through an orifice into a lower tank and out through a second orifice, and a PI controller holds
the level of the lower tank. Unlike the motor, this process is nonlinear: a controller designed at one
level behaves differently at another. The dimensions are those of a common lab rig.
uv run python examples/coupled_tanks.py
The plant¶
Water flows out of a tank through an orifice at Torricelli's speed \(\sqrt{2 g h}\), so the outflow grows with the square root of the level:
with the tank cross-section \(A = 15.5\) cm², the orifices \(a_1 = 0.32\) cm² and \(a_2 = 0.18\) cm², and a pump that delivers 3.3 cm³/s per volt (0 to 22 V). In the model each tank is an Integrator limited to 0-30 cm (the tank height) with a square-root block for the outflow.
Operating point: for the lower tank at 15 cm, the outflow is \(a_2\sqrt{2g \cdot 15} = 30.5\) cm³/s; the pump needs 9.26 V for that, and the upper tank settles at 4.74 cm. Linearized around this point, each tank is a first-order system with the time constant \(\tau_i = \frac{A}{a_i}\sqrt{\frac{2 h_i}{g}}\): 4.8 s for the upper tank and 15.2 s for the lower one. The steady-state gain from pump voltage to the lower level is \(\frac{dh_2}{dV} = \frac{K_{pump}\, q}{g\, a_2^2} = 3.2\) cm/V.
Step 1: the open-loop step¶
Set closed_loop = 0 and V_open = 10.25 (1 V more than the equilibrium) and run 400 s. The lower level rises
from 15 to 18.4 cm: 3.4 cm/V, a bit more than the linear 3.2 cm/V, because the process is nonlinear. It takes
23 s to reach 63 % of the change: the two time constants in series (15.2 + 4.8 s) make an S-shaped response.
Step 2: the PI controller¶
With closed_loop = 1 the PI controller drives the pump. The design cancels the slow lower tank: the integral
time \(T_i = 15.2\) s equals its time constant, so the loop is
\(L(s) = \frac{K_c \cdot 3.2}{T_i s (4.8 s + 1)}\). For a crossover of 0.1 rad/s (a closed loop about ten times
faster than the tank) \(K_c = 0.1 \cdot 15.2 / 3.2 = 0.47\) V/cm, with a phase margin of about 65°.

The reference steps to 17 cm at 50 s: the level follows with 0.12 cm overshoot and settles within 2 % in 44 s; the step down to 13 cm takes 38 s.
Step 3: the nonlinearity¶
At 250 s the reference drops to 5 cm, far from the design point. The controller still works, but it takes
62 s to settle, half as fast. The process gain \(dh_2/dq\) is proportional to \(\sqrt{h_2}\): at 5 cm it is only
58 % of the gain at 15 cm, so the loop crosses over at a lower frequency. Industrial controllers solve this
with gain scheduling: the gain is made a function of the operating point. Try Kc = 0.94 (twice the
gain): the step to 5 cm then settles in 30 s, at the price of more overshoot around 15 cm.
Experiments¶
| Try | What you will see |
|---|---|
Kc = 0.94 |
twice the gain: 2.2 % overshoot at 17 cm, and the step to 5 cm settles in 30 s instead of 62 s |
Kc = 0.235 |
half the gain: no overshoot, but 52 s near 15 cm and 121 s at 5 cm |
Ti = 5 |
too much integral action: the level shoots to 18 cm and drops to 3.4 cm after the step to 5 cm |
Kc = 5 |
the pump runs into its limits (0 V on the way down); with anti_windup on none (block pi in Properties) the level undershoots to 3.2 cm instead of reaching 5 cm cleanly |